Failure Analysis on Skunk-Arm of Electrical Tower

Authors

  • A. Rivai Universiti Teknikal Malaysia Melaka,
  • M.R. Said Universiti Teknikal Malaysia Melaka,

Abstract


Un-proper procedure during installation of the wire-rope could introduce unusual loading to the skunk-arm of the high-voltage electrical tower. Understanding of structural behavior of this kind of structure under different loading should be helpful to take preventive measure again possible future accidental cases. Static and buckling analyses have been performed using Finite Elements Analysis (FEA). Skunk-arm structure modelized by one-dimensional elements, combination between bar and beam. Beam elements represent main structure that are flexural members and bar elements represent stiffener that can only be in tension or compression loading. Stress distribution due to maximum static loading did not show an excessive stress value, it means no yielding occurs in the structure. But buckling factor show the maximum loading is close to the critical loading that may provoke collapse of structure in buckling mode. The result shows the mechanism of structure failure, which begin with buckling of the lower members of the skunk. In normal condition, factor of safety of 2 is taken according to maximum loading of the structure.

Downloads

Download data is not yet available.

Author Biographies

A. Rivai, Universiti Teknikal Malaysia Melaka,

Faculty of Mechanical Engineering,
Universiti Teknikal Malaysia Melaka,
Karung Berkunci 1752, Pejabat Pos Durian Tunggal,
76109 Durian Tunggal, Melaka, Malaysia

M.R. Said, Universiti Teknikal Malaysia Melaka,

Faculty of Mechanical Engineering,
Universiti Teknikal Malaysia Melaka,
Karung Berkunci 1752, Pejabat Pos Durian Tunggal,
76109 Durian Tunggal, Melaka, Malaysia

Downloads

Published

2010-06-30

How to Cite

Rivai, A., & Said, M. (2010). Failure Analysis on Skunk-Arm of Electrical Tower. Journal of Engineering and Technology (JET), 1, 149–160. Retrieved from https://jet.utem.edu.my/jet/article/view/142